 D-TRIP CHARACTERISTICS
Application Examples:
ONE POLE
ONE POLE PLUS NEUTRAL
High inrush motors, transformers, power supplies, heaters and reactive loads. Relatively long thermal trip delay and very high magnetic trip point. Prototype testing is recommended in motor applications where the relatively long thermal trip delay may not provide adequate motor overload protection. Motor-integral overload protectors are recommended, with the V-EA-D providing disconnect, backup thermal protection and additional short circuit and energy let-through protection.
1D
Rated Current 0.3A 0.5A 0.75A 0.8A 1.0A 1.6A 2.0A 2.5A 3.0A 3.5A 4.0A 5.0A 6.0A 8.0A 10A 12A 12.5A 13A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 277VAC 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB 0.3-10A (RC): 10kA; 13-60A (RC): 5kA no branch circuit protection required 0.3-63A (RC): 10kA 10000 ON/OFF operations 40C (104F) 10/0.3A - 32A = 1.4kg (3.1 lb.) 40A - 63A = 1.6kg (3.5 lb.) Top: 18-3 AWG; Bottom: 18-2 AWG 20 lb.in. Type/ Cat. No. 1DU03 1DU05 1DU075 NA 1DU1 1DU1.6 1DU2 1DU2.5 1DU3 1DU3.5 1DU4 1DU5 1DU6 1DU8 1DU10 NA NA 1DU13 1DU15 1DU16 1DU20 1DU25 1DU30 1DU32 1DU40 1DU50 1DU60 1DU63 Approvals
UL UL UL
2DN
Type/ Cat. No. 2DNU03 2DNU05 2DNU075 NA 2DNU1 2DNU1.6 2DNU2 2DNU2.5 2DNU3 2DNU3.5 2DNU4 2DNU5 2DNU6 2DNU8 2DNU10 NA NA 2DNU13 2DNU15 2DNU16 2DNU20 2DNU25 2DNU30 2DNU32 2DNU40 2DNU50 2DNU60 2DNU63 277VAC 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB 0.3-10A (RC): 10kA; 13-60A (RC): 5kA no branch circuit protection required 0.3-63A (RC): 10kA 10000 ON/OFF operations 40C (104F) 5/0.3A - 32A = 1.3kg (2.9 lb.) 40A - 63A = 1.45kg (3.2 lb.) Top: 18-3 AWG; Bottom: 18-2 AWG 20 lb.in. Approvals
UL UL UL
UL UL UL UL UL UL UL UL UL UL UL
UL UL UL UL UL UL UL UL UL UL UL
Type Designation 2 D N U -- -- -- -- (a) (b) (c) (d)
60 -- (e)
(a) = Number of Poles (b) = Trip Characteristic (c) = Blank: without neutral pole = N: with neutral pole (d) = U: UL/CSA version = R: ring tongue terminals, UL/CSA version = Blank: European version (e) = Rated Current
UL UL UL UL UL UL UL UL UL UL
UL UL UL UL UL UL UL UL UL UL
Approvals:
* * * *
* * * *
UL508 Listed
Voltage Rating Interrupting Capacity (UL/CSA - Ratings) Group Short Circuit (UL/CSA - Ratings) Interrupting Capacity (VDE - Ratings) Mechanical Endurance Calibration Temperature Standard Pack and Weight Terminal Size Acceptability Terminal Torque Basic Dimensions (Elevation View)
Not European standard rating. Please refer to page 21 for specific
applications. DC rating (Manufacturer's self certification): One pole 48VDC, two pole series 125VDC * VDE pending
91.5 mm (3.60 in.)
91.5 mm (3.60 in.)
17.5 mm (0.69 in.)
35 mm (1.38 in.)
Altech Corp.(R) * 35 Royal Road * Flemington, NJ 08822-6000 * Phone (908)806-9400 * FAX (908)806-9490 * www.altechcorp.com 12
TWO POLE
THREE POLE
Basic Dimensions (side view)
35 mm (1.38 in.)
2D
Rated Current 0.3A 0.5A 0.75A 0.8A 1.0A 1.6A 2.0A 2.5A 3.0A 3.5A 4.0A 5.0A 6.0A 8.0A 10A 12A 12.5A 13A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A Type/ Cat. No. 2DU03 2DU05 2DU075 NA 2DU1 2DU1.6 2DU2 2DU2.5 2DU3 2DU3.5 2DU4 2DU5 2DU6 2DU8 2DU10 NA NA 2DU13 2DU15 2DU16 2DU20 2DU25 2DU30 2DU32 2DU40 2DU50 2DU60 2DU63 Approvals
UL UL UL
3D
Type/ Cat. No. 3DU03 3DU05 3DU075 NA 3DU1 3DU1.6 3DU2 3DU2.5 3DU3 3DU3.5 3DU4 3DU5 3DU6 3DU8 3DU10 NA NA 3DU13 3DU15 3DU16 3DU20 3DU25 3DU30 3DU32 3DU40 3DU50 3DU60 3DU63 480Y/277VAC 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB 0.3-10A (RC): 10kA; 13-60A (RC): 5kA no branch circuit protection required 0.3-63A (RC): 10kA 10000 ON/OFF operations 40C (104F) 4/1.68kg (3.7 lb.) Top: 18-3 AWG; Bottom: 18-2 AWG 20 lb.in.
Seconds
70mm (2.76 in.)
Approvals
UL UL UL
V-EA-D Trip 0.3A Through 10A Rated Current
1.13-1.45xIN
60 40
Minutes
10 4 1
Thermal Overload "Must Trip" < 1 hr = 145% RC "Must Not Trip" > 1 hr = 113% RC
UL UL UL UL UL UL UL UL UL UL UL
UL UL
Tripping time t
UL UL UL UL UL UL UL UL UL
10 4 1 0.4 10-1 4x10-2
Seconds
10-2 4x10-3 10-3
1
2
3 4 5 6 8 10 16 20
40
100
UL UL UL UL UL UL UL UL UL UL
UL UL UL UL UL UL UL UL UL UL
Multiple of Rated Current
V-EA-D Trip 13A Through 63A Rated Current
1.13-1.45xIN 60 40
* * * *
* * * *
Minutes
10 4 1
Thermal Overload "Must Trip" < 1 hr = 145% RC "Must Not Trip" > 1 hr = 113% RC
480Y/277VAC 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB 0.3-10A (RC): 10kA; 13-60A (RC): 5kA no branch circuit protection required 0.3-63A (RC): 10kA 10000 ON/OFF operations 40C (104F) 5/1.4kg (3.1 lb.) Top: 18-3 AWG; Bottom: 18-2 AWG 20 lb.in.
Tripping time t
10 4 1 0.4 10-1 4x10-2 10-2 4x10-3 10-3
1
2
3 4 5 6 8 10 16 20
40
100
Multiple of Rated Current
"D" Magnetic Trip Parameters Rated current 0.3A to 63A. 1. Hold for a minimum of 100ms at surge of 10 times rated current. 2. Trip in under 100ms at 16 times rated current. NB: Trip curves shown comply with North American standards. For trip curves according to European standards please consult Altech.
91.5 mm (3.60 in.)
91.5 mm (3.60 in.)
35 mm (1.38 in.)
52.5 mm (2.07 in.)
Altech Corp.(R) * 35 Royal Road * Flemington, NJ 08822-6000 * Phone (908)806-9400 * FAX (908)806-9490 * www.altechcorp.com 13